SS Multi Point Averaging Flow Sensor
Ideal for Sensing Fan Flow Rates
Application:-
Zone Control in HVAC Systems

The ALM ® make SS Multipoint Averaging Flow sensor is ideal for sensing differential pressure in the inlet section of variable air volume terminal units and fan terminal units. Units can also be used to sense differential pressure at other locations in the main or branch duct systems.

The “H” port senses total pressure and “L” port senses static pressure. The difference between these signals is the differential, or velocity pressure. Which also measures air velocity.

SPECIFICATIONS

Service: Air and compatible gases.
Wetted Materials: SS 304
Temperature Limits: Operating: upto 1400 C
Connection: 1/4 (6mm) I.D. tubing for 3/8 (10mm) O.D.tubing.
Mounting Orientation:

Sr No.

LONGEST SIDE OF THE DUCT CROSS SECTION IN MM

RECOMMENDED LENGTH: MM

STANDARD LENGTH AVAILABLE WITH ALM®: MM

1.

400

300 (AVAILABLE IN SS 304)

300 (ALM ® MAKE)

2.

500

375 (AVAILABLE IN SS 304)

400 (ALM ® MAKE)

3.

600

450 (AVAILABLE IN SS 304)

450 (ALM ® MAKE)

4.

700

525 (AVAILABLE IN SS 304)

500 (ALM ® MAKE)

5.

800

600 (AVAILABLE IN SS 304)

600 (ALM ® MAKE)

6.

900

675 (AVAILABLE IN SS 304)

700 (ALM ® MAKE)

7.

1000

750 (AVAILABLE IN SS 304)

800 (ALM ® MAKE)

8.

1100

825 (AVAILABLE IN SS 304)

800 (ALM ® MAKE)

9.

1200

900 (AVAILABLE IN SS 304)

900 (ALM ® MAKE)

10.

1300

975 (AVAILABLE IN SS 304)

1000 (ALM ® MAKE)

11.

1400

1050 (AVAILABLE IN SS 304)

1100 (ALM ® MAKE)

12.

1500

1200 (AVAILABLE IN SS 304)

1200 (ALM ® MAKE)



Lightweight Averaging Flow Sensor
Ideal for Sensing Fan Flow Rates

The Series SSS-1000 Lightweight Flow Sensor is ideal for sensing differential pressure in the inlet section of variable air volume terminal units and fan terminal units. Units can also be used to sense differential pressure at other locations in main or branch duct systems.
The “H” port senses total pressure and the “L” port senses static pressure. The difference between these signals is the differential, or velocity pressure.
For Models SSS-1002 to SSS-1005, up to four sensing points and lengths of 3-5/32” to 9-29/32” (8.02 to 25.26 cm) to accommodate box size diameters of 4” to 16” (10.16 to 40.64 cm) are available. For Models SSS-1006 to SSS-1011, up to 10 sensing points and lengths from 12-1/2” to 23-29/32” (31.75 to 60.72 cm) to accommodate appropriately sized box diameters.


APPLICATION
Zone Control in HVAC Systems
SPECIFICATIONS
Service: Air and compatible gases.
Wetted Materials: ABS/Polycarbonate (UL94-5V).
Temperature Limits: Operating: 40 to 120*F (4 to 49*C);
Storage: -40 to 140*F (-40 to 60*C).
Connection: 1/4 (6mm) I.D. tubing for 3/8 (10mm) O.D. tubing
SSS – 1000
Weight: 1oz (28g).
Lightweight Averaging Flow Sensor

Model

Length ( Dimension A)

SSS-1002
SSS-1003
SSS-1004
SSS-1005
SSS-1006
SSS-1007
SSS-1008
SSS-1009
SSS-1010
SSS-1011

3-5/32 (8.02 cm)
5-13/32 (13.73 cm)
7-21/32 (19.55 cm)
9-29/32 (25.26 cm)
12- 1/2 (31.75 cm)
14-3/4 (37.47 cm)
17-1/8 (43.50 cm)
19-13/32 (49.29 cm)
21-21/32 (60.72 cm)
23-29/32 (60.72 cm)



OTHER/ CUSTOM SIZES AVAILABLE ON REQUEST
 
Copyright © 2008. ALM .