NEMA
4X Enclosure, 0.25% F.S. Accuracy, Ranges from
0-1 in. w.c. to 0-100 psid |
Positive,
negative and differential pressures can be measured
within a full span accuracy of ±0.25%with
the Series 616W Differential Pressure Transmitter.Units
are enclosed in a polycarbonate case,rated NEMA
4X (IP66)and operate by sensing the pressure of
air and compatible gases then sending a standard
4-20 mA output signal.Design enables operation
in 2-wire current loops.A wide range of models
are available factory calibrated to specific ranges.The
span and zero controls are for use when checking
calibration.They are not intended for re-ranging
to a significantly different span.The LCD (as
shown above)allows local indication of pressure.(If
LCD is not needed,drop from model number).
|
Service:
Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: ±0.25% F.S.,
display accuracy ±0.5%.
Stability: +1% F.S./yr.
Temperature Limits: 0 to 140°F
(-17.8 to 60°C).
Compensated Temperature Limits:
20 to 120°F (-6.67 to 48.9°C).
Pressure Limits: See chart.
Thermal Effect: ±0.02%
F.S./°F (0.0012% F.S./°C).
Power Requirements: 10-35 VDC
(2-wire).
Output Signal: 4 to 20 mA.
Zero and Span Adjustments: Potentiometers
for zero and span.
Loop Resistance: DC; 0-1250 ohms maximum.
Current Consumption: DC; 38 mA
maximum.
Electrical Connections: Screw-type
terminal block.
Process Connections: Barbed,
dual size to fit 1/8? and 3/16? (3.12 and 4.76
mm) I.D. rubber or vinyl tubing.
Enclosure Rating: NEMA 4X (IP66).
Mounting Orientation: Vertical,
consult factory for other position orientations.
Weight: Without LCD 8.8 oz. (249
g); with LCD 9.6 oz (272 g).
Agency Approvals: CE. |