Ideal
for Building Automation Systems |
The
Series AVU Air Velocity Transmitter is
ideal for a wide range of HVAC measurement and
control applications,particularly in complete
building control and energy management systems.The
Series AVU offers 5%accuracy at a surprisingly
low cost,with six units covering ranges from 0-785
fpm to 0-3150 fpm,with either 4-20 mA or 0-10
VDC output. The Series AVU Transmitter operates
by measuring the heat loss from one of the two
sensing elements in the air stream,then calculating
the air velocity.Units are virtually immune to
driftdue to the design of the sensing element,which
makes the transmitter accurate over the whole
air velocity range.
|
Service:
Clean air and compatible, non-combustible gases.
Accuracy: ±5% of full
scale.
Response Time (90%): 5 sec (typical).
Temperature Limits: 32 to 122°F
(0 to 50°C).
Humidity Limit: 0-90% RH, non-condensing.
Power Requirements: -A models
24 VDC +10% -15%; -V models 24 VDC or 24 VAC +10%
- 15%.
Output Signal: -A models 4-20
mA current loop; -V models 0-10 VDC.
Loop Resistance: (-A models)
700 ohms.
Current Consumption: 60 mA +
output current.
Max. Start Up Current: 85 mA;
10 V.
Output Current Limit: (-V models)
>10 mA.
Electrical Connections: Screw
terminal. Cable gland for 4-8 mm wire (16 gauge
wire).
Enclosure Rating: NEMA 6 (IP67)
except sensing point.
Probe Dimensions: 9.45 x .75?
(240 x 19 mm).
Mounting Orientation: Unit not
position sensitive. Probe must be aligned with
airflow.
Weight: 8.8 oz (250 g).
Agency Approvals: CE. |